Skip common site navigation and headers
US EPA
RCRA Online
Begin Hierarchical Links You are here: EPA Home >> Wastes >> Information Sources >> RCRA Online >> Document Record Detail End Hierarchical Links
Welcome What's New Topics Full Text Search Advanced Search Help

Document Record Detail



Full Document:
Title:HAZARDOUS WASTE TANKS/CONTAINERS - CAPACITY OF SECONDARY CONTAINMENT
RCRA Online Number:13190
Date:06/01/1988
To:NA
From:NA
Organization of Recipient:NA
Description: A vault containing both tanks and containers must be able to contain 100% of the largest tank. If that volume is greater than 10% of the containers’ volume, then no additional capacity is needed. 110% capacity is not required.
Regulatory Citation(s) : 264.175(b)(3), 264.193 EXIT disclaimer
Statutory Citation(s):NA Read US Code 42, Chapter 82 EXIT disclaimer
Topic(s):Containers; Hazardous Waste; Storage; Tanks; TSDFs
Approximate Number of Hardcopy Pages:2
EPA Publication Number:530-SW-88-056F
RPPC Number (if applicable): 9483.1988(14)
Official OSW Policy:No

 

 