Title:PRESSURIZED PIPING SYSTEMS WITH AUTOMATIC SHUT-OFF DEVICES
RCRA Online Number:13005
Date:08/03/1987
To:Love
From:Dellinger
Organization of Recipient:Allied Corporation
Description: A pressurized piping system with an automatic shut-off device is exempt from the secondary containment requirement for tank ancillary equipment. The exemption applies in the absence of welded flanges, welded joints, welded connections, sealless valves, and sealless or magnetic coupling pumps.
Regulatory Citation(s) : 264.193(f)(4), 265.193(f)(4) EXIT disclaimer
Statutory Citation(s):NA Read US Code 42, Chapter 82 EXIT disclaimer
Topic(s):Hazardous Waste; Tanks; TSDFs
Approximate Number of Hardcopy Pages:2
EPA Publication Number:NA
RPPC Number (if applicable): 9483.1987(14)
Official OSW Policy:No

 

 