| Full Document: |  |
| Title: | CONTAINMENT AND DETECTION OF RELEASE FROM HAZARDOUS STORAGE TANK SYSTEMS |
| RCRA Online Number: | 13195 |
| Date: | 06/03/1988 |
| To: | Conway and Marz |
| From: | Kline |
| Organization of Recipient: | Owen Ayres and Associates, Inc. |
| Description: | Daily visual monitoring is acceptable for a hazardous waste tank that is elevated above the ground. A grooved concrete pedestal is acceptable leak detection. A secondary containment system must be able to contain 100 percent of the largest hazardous waste tank plus rain from a 25-year 24-hour storm. |
| Regulatory Citation(s) : | 264.193(c)(3), 264.193(e)(1), 265.193(c)(3), 265.193(e)(1)  |
| Statutory Citation(s): | NA Read US Code 42, Chapter 82  |
| Topic(s): | Hazardous Waste; Tanks; TSDFs |