Title:SHAM RECYCLING POLICY AS IT PERTAINS TO THE BOILER AND INDUSTRIAL FURNACE RULE
RCRA Online Number:13680
Date:06/07/1994
To:Lesslie
From:Shapiro
Organization of Recipient:State of Kansas
Description: The BIF rule supersedes the sham recycling policy of a minimum 5000 Btu/lb heating value for waste (56 FR 7183; February 2, 1991). A product is waste-derived if a furnace burns hazardous waste fuels with a heating values less than 5000 Btu/lb, unless the facility demonstrates legitimate energy recovery, or unless the is waste is excluded via the use in a manner constituting disposal standards in Section 266.20(b). The minimum fuel value is determined on an as-generated, not as-fired basis. Blending to augment the as-generated heating value cannot be used to pass threshold. The heating value can be increased through legitimate treatment.
Regulatory Citation(s) : 266.20(b), 266.100 EXIT disclaimer
Statutory Citation(s):NA Read US Code 42, Chapter 82 EXIT disclaimer
Topic(s):Boilers; Burning; Combustion of Hazardous Waste; Disposal; Hazardous Waste; Hazardous Waste Recycling; Industrial Furnaces; Treatment
Approximate Number of Hardcopy Pages:2
EPA Publication Number:NA
RPPC Number (if applicable): 9494.1994(03)
Official OSW Policy:Yes

 

 